When auto_enabled or fault_locked changes externally, the engine task
wakes via notify but previously only pushed WS on the next state
transition (potentially seconds later). Now push the fresh runtime
immediately in the notify.notified() arm so the frontend reflects
the change without delay.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
- Engine now spawns one async task per enabled unit (supervised every 10s)
- wait_phase uses sleep_until + select! for precise timing; 500ms fault-tick
runs inside each phase so fault/comm is still checked promptly
- WS UnitRuntimeChanged pushed only on state transitions, not every tick
- ControlRuntimeStore gains notify_unit/get_or_create_notify for instant
wake-up when handlers change auto_enabled or fault_locked
- UnitRuntime: remove last_tick_at, current_run/stop/distributor_elapsed_sec;
add display_acc_sec (snapshot at transition, avoids mid-cycle jitter)
- accumulated_run_sec now increments by exact run_time_sec*1000 per cycle
- unit.state_changed events no longer written to DB (too frequent)
- Frontend: show display_acc_sec instead of accumulated_run_sec
- styles: event-card flex-shrink:0 fixes text overlap under flex column
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
When accumulated_run_sec reaches acc_time_sec, the coal feeder must be stopped
before entering DistributorRunning state. Previously the feeder was left running
while the distributor also ran, which is incorrect per the control spec.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Instead of always patching the local cache, first attempt to write the RUN
point value through the normal OPC UA path. If the proxy accepts the write,
write_point_values_batch already emits PointNewValue locally so no extra work
is needed. Only fall back to direct cache patching when the write is rejected.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
- validator: reject equipment start/stop when unit auto_enabled
- engine: fix stop_time_sec==0 causing infinite Stopped state (never starts)
- engine: call simulate_run_feedback after auto commands when SIMULATE_PLC=true
- command: extract simulate_run_feedback to shared module (was private in handler)
- web: disable Start/Stop buttons when unit auto is active; sync on WS runtime update
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>