docs(api): document rem_local field and REM control behavior
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
This commit is contained in:
parent
737f32af8f
commit
7a8b0e6ce7
18
API.md
18
API.md
|
|
@ -290,10 +290,16 @@
|
|||
"fault_locked": false,
|
||||
"flt_active": false,
|
||||
"comm_locked": false,
|
||||
"manual_ack_required": false
|
||||
"manual_ack_required": false,
|
||||
"rem_local": false
|
||||
}
|
||||
```
|
||||
|
||||
`rem_local` 说明:
|
||||
|
||||
- `true`: 单元下存在设备 REM 信号为本地模式(REM=0,信号质量正常)
|
||||
- `rem_local = true` 时,自动控制会被强制停止,且禁止重新启动,直到所有 REM 恢复远程
|
||||
|
||||
`state` 枚举:
|
||||
|
||||
- `stopped`
|
||||
|
|
@ -328,6 +334,8 @@
|
|||
- `unit.fault_acked`
|
||||
- `unit.comm_locked`
|
||||
- `unit.comm_recovered`
|
||||
- `unit.rem_local` — 设备切换为本地模式,自动控制已停止(warn)
|
||||
- `unit.rem_recovered` — 设备切换回远程模式,自动控制需手动重新启动(warn)
|
||||
- `equipment.start_command_sent`
|
||||
- `equipment.stop_command_sent`
|
||||
|
||||
|
|
@ -336,12 +344,13 @@
|
|||
所有控制命令在执行前都会校验:
|
||||
|
||||
- 信号质量
|
||||
- REM 状态
|
||||
- REM 状态(REM=0 时拒绝手动指令)
|
||||
- FLT 状态
|
||||
- 单元 `auto_enabled`
|
||||
- 单元 `comm_locked`
|
||||
- 单元 `fault_locked`
|
||||
- 单元 `manual_ack_required`
|
||||
- 单元 `rem_local`(自动控制启动时额外校验)
|
||||
|
||||
### POST `/api/control/equipment/{equipment_id}/start`
|
||||
|
||||
|
|
@ -361,6 +370,7 @@
|
|||
- `fault_locked = false`
|
||||
- `comm_locked = false`
|
||||
- `manual_ack_required = false`
|
||||
- `rem_local = false`(有设备处于本地模式时不允许启动)
|
||||
|
||||
成功响应:
|
||||
|
||||
|
|
@ -382,6 +392,7 @@
|
|||
- `fault_locked = true`
|
||||
- `comm_locked = true`
|
||||
- `manual_ack_required = true`
|
||||
- `rem_local = true`
|
||||
|
||||
说明:
|
||||
|
||||
|
|
@ -523,8 +534,10 @@ data: log stream read failed
|
|||
"state": "running",
|
||||
"auto_enabled": true,
|
||||
"fault_locked": false,
|
||||
"flt_active": false,
|
||||
"comm_locked": false,
|
||||
"manual_ack_required": false,
|
||||
"rem_local": false,
|
||||
"accumulated_run_sec": 3600000,
|
||||
"display_acc_sec": 3600000
|
||||
}
|
||||
|
|
@ -564,3 +577,4 @@ data: log stream read failed
|
|||
- 控制引擎现在会在每轮单元循环中重新加载设备和角色映射,而不是只在任务启动时加载一次。
|
||||
- 设备和点位的控制相关配置变更后,会主动唤醒对应单元任务,使新配置尽快生效。
|
||||
- 日志流默认跟随最新日志文件,适配日志轮转场景。
|
||||
- REM 信号为本地模式(REM=0)时,手动控制指令(start/stop)和自动控制启动均被拒绝;若自动控制正在运行,引擎会立即停止并记录 `unit.rem_local` 事件。REM 恢复远程后记录 `unit.rem_recovered`(warn),自动控制需操作员手动重新启动。
|
||||
|
|
|
|||