feat(control): reject manual commands when unit is fault/comm locked
This commit is contained in:
parent
628553f2b8
commit
684ca9da85
|
|
@ -115,7 +115,36 @@ pub async fn validate_manual_control(
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
let command_value_type = monitor_guard
|
drop(monitor_guard);
|
||||||
|
|
||||||
|
// Runtime state checks — block commands if unit is locked
|
||||||
|
if let Some(unit_id) = equipment.unit_id {
|
||||||
|
if let Some(runtime) = state.control_runtime.get(unit_id).await {
|
||||||
|
if runtime.comm_locked {
|
||||||
|
return Err(ApiErr::Forbidden(
|
||||||
|
"Unit communication is locked".to_string(),
|
||||||
|
Some(json!({ "unit_id": unit_id })),
|
||||||
|
));
|
||||||
|
}
|
||||||
|
if runtime.fault_locked {
|
||||||
|
return Err(ApiErr::Forbidden(
|
||||||
|
"Unit is fault locked".to_string(),
|
||||||
|
Some(json!({ "unit_id": unit_id, "manual_ack_required": runtime.manual_ack_required })),
|
||||||
|
));
|
||||||
|
}
|
||||||
|
if runtime.manual_ack_required {
|
||||||
|
return Err(ApiErr::Forbidden(
|
||||||
|
"Fault acknowledgement required before issuing commands".to_string(),
|
||||||
|
Some(json!({ "unit_id": unit_id })),
|
||||||
|
));
|
||||||
|
}
|
||||||
|
}
|
||||||
|
}
|
||||||
|
|
||||||
|
let command_value_type = state
|
||||||
|
.connection_manager
|
||||||
|
.get_point_monitor_data_read_guard()
|
||||||
|
.await
|
||||||
.get(&command_point.point_id)
|
.get(&command_point.point_id)
|
||||||
.and_then(|item| item.value_type.clone());
|
.and_then(|item| item.value_type.clone());
|
||||||
|
|
||||||
|
|
|
||||||
Loading…